Variable Air Volume (VAV) is the most used HVAC system in commercial buildings. In this article we’ll discuss the Variable Air Volume system and single duct VAV boxes with reheat coils. The Air Handler varies the amount of air flow (CFM) at the overall system level based on the demand required by the zone level VAV boxes, which vary air flow based on their local demand.
E3 Green Technology Product Page
To watch the Video of this presentation, scroll to the bottom.
The VAV box regulates the flow (CFM) to a zone in relationship to the demand of the temperature sensor in the space.
Variable air volume is more energy efficient than constant volume flow because of the reduction in fan motor energy due to reducing fan speed (RPM) at partial load. As the cooling or heating demand is reduced because of a mild temperature day, the VAV Air Handler system can reduce the amount of air flow (CFM) by reducing the fan speed.
The air handler will deliver a constant temperature of 55ºF (13 ºC) supply air to the VAV boxes. While the supply air temperature stays constant the volume (CFM) of air will vary based on the total demand of all the zones on the system. There are several control strategies to adjust the speed of the fan which we’ll discuss below.
As the VAV boxes open or close due to demand called for by the temperature sensor in the space, the pressure in the main supply air duct will either increase or decrease. This pressure change is picked up by a static pressure sensor in the main supply air duct.
As the pressure increases in the main supply duct because the VAV boxes are closing their dampers and are adjusting their dampers towards the minimum open setting, the air handler supply fan VFD slows down the fan. The opposite will happen due to the VAV boxes opening because of increased demand and the dampers are opening, in this case the VFD will cause the supply fan to speed up when the pressure in the main supply air duct drops.
The VFD will try to maintain the speed (RPM) of the fan so that the static pressure in the duct at the location of the static pressure sensor maintains some minimum set-point, such as 1.25” sp. The static pressure sensor sends a signal to the VFD and the speed of the fan is adjusted according to the set-point required.
The VAV box at the zone level will operate in one of three modes: Cooling Mode that varies the flow rate (CFM) to meet a temperature setpoint; a Dead-Band Mode where the temperature setpoint is satisfied and the box is at minimum flow (CFM); and a Reheat Mode for when the space requires heat.
As you can see in the diagram above the VAV Damper goes from a minimum of 30% open, whatever the minimum required to meet ASHRAE 62, all the way to the damper being 100% open.
There are basically three modes in this control strategy. Mode #1 Is the Cooling Mode where the heating hot water control valve is closed and the VAV damper modulates from 30% to 100% open in order to satisfy the temperature sensor. Next is Mode #2 Dead Band Mode is when there is no need for cooling or heating, so the damper stays in its minimum position to meet the ventilation requirements of ASHRAE 62. And Mode #3 is the Heating Mode where the VAV box damper remains in the minimum position and the heating hot water valves modulates open to satisfy the heating requirements of the space.
The VAV box has a damper at its inlet moved by an actuator that is controlled by the controller that takes its command from a temperature sensor. The process is very simple. When the temperature sensor in the space calls for cooling it sends a command to the VAV box controller which then adjust the supply air flow rate (CFM). The adjustment is done by an actuator rotating the VAV box inlet damper either open or closed in increments.
Before we get any deeper into this subject we need to cover the basics of zoning. Zoning is how the Engineering divides up the building into separate VAV zones, with each zone getting its own VAV box. To keep cost down its best to limit the amount of VAV boxes used, as each box adds additional cost for material, labor, controls and electrical.
After a heating and cooling load is completed on a building, the spaces will be divided up into zones. Each individual zone will have similar load profiles and be served by the same VAV box. A typical individual zone maybe offices that share a southern glass exposure or interior spaces. Look for a Zone drawing in any set of mechanical plans that has a large area broken down into zones. (See example of a Zone Map Drawing below)
The idea of zoning is to breakdown large areas of a building into smaller zones with similar load profiles. When a zone on the south facing portion of a building is calling for maximum cooling, the north facing zones may be in minimum cooling or heating mode. Zoning allows different spaces the ability to provide cooling or heating and vary the flow (CFM) depending on the demand of that zone’s temperature sensor.
All the zones on a floor of a high-rise maybe fed from the same air handler, but each zone can adjust its CFM according to their specific needs. Depending on the size of the floor plate, there maybe two Air Handlers per floor, or for smaller floors the Air Handler may feed more than one floor. The Air Handler can be located on the floor within a mechanical room or located on the roof.
The supply air main is considered the high side of the system. The high side being the main supply duct from the air handler to the inlet of each VAV box. The main is considered upstream of the VAV box, while downstream of the box is considered the low-side supply.
The air handler will provide 55 F degree (13 Celsius) supply air to the VAV box. The Variable Air Volume VAV box will then determine how much air (CFM) to pass through to the space based on the demand of the space. The air handler is sized to meet the maximum block load of the area it serves. The block load is basically the peak heating or cooling load of all the zones combined. It is not the total CFM of all the peaks of each zone, but the total based on the worst month, day and time of year where the total block is at its maximum load.
Each zone above is reacting differently to the early morning sun. Some zones are in cooling mode with their dampers at different percentages of being open, while other zones are in heating and one zone is off and receiving minimum air for ventilation. This is a very basic diagram of how zones may differ and why it’s important to consider how spaces are grouped together, as each space may have a different solar exposure and cooling load profile. As the sun travels across the sky the zone dampers will open or close depending on their need for heating or cooling.
Corner spaces are often difficult to include with other spaces because they have two exposures. It’s like living on the corner in your block, you have two streets. Looking at the image we can see that there are two cooling zones between corner spaces that are on the south exposure that could be grouped into one zone, Zone #5 below. The same is true for the two zones between corner spaces on the North exposures, Zone #2. If you had interior zones they would be separated from any exterior zone because interior zones are often exclusively in cooling mode due to internal heat gains and the lack of heat loss from any exterior surfaces.
During cooling mode, the Variable Air Volume VAV box will modulate between a minimum CFM setpoint and the calculated design maximum cooling CFM setpoint based on the zones peak cooling demand. When the hot summer arrives and the sun shines through windows and conducts heat through the walls and roofs, the need for cooling will be sensed by the temperature sensors in the space which will call for the VAV box to open its damper and let more cold air into the room. Or, if you’re in a room located within the interior of the building, like a conference room, then the heat from the people, lights and plug loads will cause the temperature sensor to initiate an opening of the VAV box damper for more cold air.
For exterior zones and in certain cases interior zones there will be a reheat coil or an electric heater attached to the VAV box The reheat coil can be served by heating hot water, steam or electric. When in heating mode, the flow (CFM) through the box will be at a minimum setpoint to avoid wasting energy. Remember that the air handler is sending the VAV box 55 F degree (13 Celsius) supply air which was most likely cooled by chilled water from a chiller.
This primary supply air will also bring a percentage of mandatory ventilation air (Outside Air). In some systems the supply air temperature could be increased to a temperature that is just cool enough to cool the most-demanding zone with its VAV box set to maximum flow, thereby saving additional energy.
The heating hot water valve will modulate open providing a range of heating hot water flow (GPM) to meet the heating load. The minimum CFM setpoint can be somewhere between 30% and 50% of the maximum cooling setpoint. Minimums are set by some code jurisdiction so that the minimum ventilation rate is always achieved. In California see Title-24 Sec 120.1 Requirements for Ventilation and Indoor Air Quality. See Ventilation section next.
Using electric heat is not approved in various jurisdictions. Check your local code for approved sources for the heating requirements.
We’ll mention two control strategies for optimizing energy efficiency using a VAV system. These are the 1) Constant Static Pressure Control Method, and 2) Static Pressure Reset. (Required if there is a DDC system to the zone level)
When the VAV boxes are connected to a building automation system that monitors the function and status of the boxes there are various options for control. This is based on using a DDC system.
Usually, a pressure sensor is installed 2/3 rds. of the way down the main supply air duct. When VAV boxes start closing their dampers because they need less cooling an increase in pressure will occur. When the static pressure in the supply duct increases due to the VAV boxes closing their inlet dampers the static pressure in the main supply air duct increases.
The pressure sensor in the duct will send a signal to the Variable Frequency Drive (VFD) causing the supply and return fans to slow down or reduce its RPM. If the pressure in the duct decreases because the VAV boxes are opening due to the need for additional cooling, the pressure sensor will send a signal to increase the fan speed (RPM).
The pressure sensor is set to maintain a constant pressure in the main supply duct which often causes excess static pressure to be provided when compared to option two below. The reduction in the fan speed provides energy savings.
The use of this strategy is required by Title-24 (California) and ASHRAE 90.1 for system that have DDC to the zone level. The static pressure setting in the main supply duct is reduced to a point where one VAV box damper is nearly full open. This is the zone that requires the most pressure. This would require that the VAV box actuators can report their damper position, best performed with an analog output. Look for Trim and Respond logic for more information.
These options provide a good opportunity to save energy by reducing the fan speed and possibly increasing the supply air temperature in small increments with continuous polling. If the supply temperature can be reset above the economizer set point, then the compressors can stage off and the cooling can be provided by modulating the return air and outside air dampers to deliver the desired supply air temperature.
Using a DDC control system with VAV boxes that have a flow station and temperature sensor at the supply air discharge the system can determine the amount of reheat.
Q = CFM x 1.08 x Delta-T
Q = Btu/Hr
1.08 = A constant based on standard air conditions
Delta-T = (Discharge Air Temperature – Primary Supply Air Temperature)
The building automation system can track and trend over long periods of time the following: Damper position, static pressure, reheat valve position, airflow rate (CFM), supply air temperature, zone temperature and occupancy status.
There are other types of VAV boxes not discussed here such as: Fan Powered VAV Box, VAV Mixing Box (Dual Duct Systems), CAV (Constant Air Volume).
Ventilation air (Outside Air) is required for all occupied spaces according to ASHRAE standard 62.1. When using VAV boxes the minimum volume setting of the box needs to ensure the larger of the following:
1. 30 percent of the peak supply volume;
2. Either 0.4 cfm/sf or (0.002 m3/s per m2) of conditioned zone area; or
3. Minimum CFM (m3/s) to satisfy ASHRAE Standard 62 ventilation requirements. VAV terminal units must never be shut down to zero when the system is operating. Outside air requirements shall be maintained in accordance with the Multiple Spaces Method, Equation 6-1 of ASHRAE Standard 62 at all supply air flow conditions.
The use of Variable Air Volume (VAV) has been shown to save energy when combined with a supply fan VFD’s. As the demand in the spaces fluctuate the VAV box dampers open or close proportionately and the air handler fans respond through various control strategies. Variable air volume systems save more energy than a constant volume system.
A variable air volume (VAV) system adjusts the amount of air delivered by a fan to condition (heat or cool) a space based on demand. This can be accomplished in either a single zone or multi-zone application. The units primarily utilize air conditioning in cooling mode.
In nearly all HVAC systems, the amount of heating and cooling required to maintain desired space conditions are variable. There are many factors that fluctuate impacting the heating and cooling load: envelope load (outdoor air temperatures and construction materials), solar load (sun position and shading), and internal loads (the number of people and their activity, the operation of heat producing equipment, lights, etc.). The system is sized for the peak (worst design case) heating and cooling load, but if the system were to operate at these peak capacities all the time, the space would be excessively heated or cooled.
HVAC systems can address this variability in one of three ways:
Constant Air Volume / Constant Temperature (CV/CT),
Constant Air Volume / Variable Temperature (CV/VT),
Variable Air Volume / Constant Temperature (VAV/CT).
This definition focuses on the third and commonly applied option, VAV, because of its many benefits.
Want more information on VAV Control System? Feel free to contact us.
Efficient variable air volume systems were made possible through the introduction of variable frequency drives (VFDs) and have become the industry standard today. A VFD controls the speed of a fan altering the amount of air distributed. When a space experiences part-load conditions, rather than turning the system off or changing the delivery air temperature as done in a constant volume system, the VAV system reduces the amount air delivered to the space enabling it to save energy while still satisfying occupant comfort and ventilation needs.
Variable air volume systems can be classified into two distinct categories - single zone or multi-zone. Knowing the difference is important because they operate differently and are appropriate for different HVAC applications.
Single zone VAV systems utilize a single thermostat to determine the need for heating or cooling. Since the supply air temperature is constant (~55°F when cooling and ~20°F above the room temperature set point when heating), the fan speed is sped up or slowed down based on this temperature setpoint from a sensor in the supply duct. Once the space temperature has been satisfied, the fan will slow down, reducing the air volume and saving energy. In a DX cooling application, the compressor(s) can stage up or down to maintain the desired air temperature also reducing energy use. For example, if the supply air temperature goes below 55°F, the compressor will start to stage down. Because there is only one thermostat per unit, if multiple spaces are being cooled from one unit, the space(s) without the thermostat will likely be more uncomfortable. Commonly, multiple single zone VAV units can be used in larger buildings with many rooms, such as schools or offices.
For a multi-zone VAV system, a central unit provides air conditioning to multiple spaces, such as offices in a commercial building. Each space, or zone, has what is called a VAV terminal or VAV box. There are several different VAV boxes that can be selected based on application: single duct, dual duct, or series fan-powered VAV terminals. Single duct and fan powered VAV systems are the two most common systems, where a single duct system uses one supply duct system. Other systems not as common would be a dual duct system, however they are not as common due to the expense in additional supply duct materials.
The VAV box utilizes a damper that will open or close based on a thermostat demand. If the space temperature rises above the thermostat setting, the damper will open to allow more airflow into the zone. Once the thermostat sends a signal indicating the space temperature is satisfied, the dampers will close to a minimum position to allow for ventilation. As dampers in the zones open and close, the static pressure in the ductwork will change. The supply fan will modulate based on the static pressure value, which is provided with a static pressure sensor. A defined static pressure range is set based on the application. For example, if the static pressure drops below the setpoint, the fan will speed up. This will happen due to the VAV dampers opening. This control of the fan can lead to increased fan energy savings for the unit.
In the heating seasons, sometimes a space may need a little heating. VAV boxes can be equipped with electric heat strips or hot water coils to control the heating into the space. It is rare that all zones will need heating so it does not make sense to control the heating at the central unit for a multi-zone setup.
Since multi-zone VAV boxes cannot provide cooling at the zone level, a central unit is required to produce the cool air. This central unit could be a direct expansion (DX) or chilled water air handling unit or roof top unit. Within the multi-zone system, you have the following key components:
Static pressure sensor: used to control the supply fan speed.
Supply air temperature sensor: used to control the compressor modulation (if a DX system) or chilled water valve (chilled water system).
VAV boxes: controls the amount of airflow delivered to the space.
Thermostat: used in each zone to control the VAV box damper position.
To optimize the system operation, reduce energy use, and to conform with the energy codes, sophisticated HVAC system controls are needed for multi-zone VAV systems. These direct digital controls (DDC) ensure precision of airflow delivered to the space.
Multi-zone VAV systems are most commonly selected for their ability to provide simultaneous heating and cooling within the same building using a centralized unit. The ability to provide greater occupant control and comfort is a wonderful benefit to this system but there are other positive attributes that should not be overlooked.
The use of a centralized unit allows consolidated maintenance because this unit contains the fan, filters, and coils. This eliminates the need to interrupt or schedule maintenance around the occupant and reduces maintenance time of facility personnel compared to a distributed system. Although there are VAV terminals dedicated to each zone throughout the building, these are basic units requiring minimal maintenance. Utilizing a computerized maintenance management system (cmms) can help leverage proper maintenance schedules for servicing the system.
When dampers in VAV terminals reduce the air delivered to spaces from the central unit in response to zone loads, the total amount of cool air produced by the central unit decreases. Since fans are the most significant consumer of energy in many HVAC systems, VAV systems are a very good solution for applications prioritizing comfort, reduced energy use, and sustainable design.
Lastly, but certainly not less important, is the constant lower air temperature produced by the VAV system. This provides better dehumidification at part load conditions compared to constant volume systems. This is significant because high humidity can result in decreased indoor air quality and introduce the potential for mold growth; not only decreasing comfort but possibly compromising occupant health.
Proper design and installation are always priorities with any HVAC system. However, with VAV systems, especially multi-zone, zoning and ventilation are especially important. Factors such as understanding building layout and orientation, occupancy schedules, zoning of the spaces, and thermostat placement all become critical for ensuring maximum comfort and energy efficiency. Ventilation is just as important in a VAV system as other HVAC systems. Airflow reduces as zone heating/ cooling demand decreases, but the amount of air delivered to a zone cannot go to zero when it is occupied due to ventilation requirements. Calculation that can be complex are needed to determine how the system will efficiently function with the fluctuations in airflow. Sometimes, it is easier to pair a dedicated outdoor air system (DOAS) with a multi-zone VAV unit to control the ventilation necessary.
Noise levels in a space can be an important factor for the design of the system. Placing VAV boxes above unoccupied spaces with branch ductwork to the space can help limit noise in the space. in some cases the VAV boxes may produce some air noise as the damper opens and closes. Noise reducing upgrades can be made for the VAV boxes to ensure a quieter operation and create less disturbance to occupants in the space.
Space availability and coordination are both attributes of a multi-zone VAV system that cannot be ignored. Using a large, centralized unit to deliver air to many zones requires large ductwork to be connected to the unit and distributed in the ceiling plenum. When a central unit is located inside the building, a mechanical room large enough to house the unit with adequate space to service the equipment is needed. In larger applications, the use of multiple central units to serve a single building may be preferred when considering the space available, the building use schedule, and the desire for reduced risk in case of failure. Using multiple central units can also contribute to greater energy savings.
Recognizing the many benefits of multi-zone VAV systems, AAON has addressed the two most common barriers associated with this system – lack of interior space for the central unit and the cost of customized controls. Not having space for an interior mechanical room to house a traditional air handling unit (AHU) as the central cooling unit commonly eliminates multi-zone VAV from consideration as a system option. In the past, the only way around this was to upgrade an AHU to have an expensive weatherproof enclosure or to build a penthouse to enclose the unit. AAON’s packaged roof top units (RTUs) provide a better and more cost-effective solution.
AAON’s RTUs are designed to be placed outdoors, arrive as a packaged piece of equipment simplifying installation, and their customizable selection allows it to perform as the central unit even under the most unique conditions. Not only can an AAON RTU be used as the central unit, but AAON can integrate multi-zone VAV controls. Integration of AAON controls reduces first cost compared to other systems. This allows multi-zone VAV to be a solution in applications where it was cost prohibitive in the past. AAON utilizes advanced integrated controls to also eliminate the need for expensive, overly complicated BAS/BMS systems. Besides the cost savings of integrated controls, the start-up process is streamlined by not having to coordinate between multiple vendors. Add the energy savings that occur over the life of the building because central unit performance is optimized with integrated controls, it becomes clear that AAON has provided a complete cost competitive solution.
These same controls can also be integrated into other AAON equipment when used as the central cooling unit in a multi-zone VAV system. AAON AHUs provide best-in-class flexibility whether considering indoor units, outdoor units, packaged units or split units. With the many features available with an AAON unit and the ease of customization, AAON can meet the specific needs of any building while providing assurance that both superior value and performance are attained.
Multi-zone VAV is a type of HVAC system that varies the airflow to different rooms or groups of rooms in a building based on its heating or cooling needs.
A multi-zone VAV system employs a control system to monitor the space needs and adjusts the airflow to the space from a central unit and air temperature using a VAV terminal. The central unit delivers cool air to all the zones in the building and the VAV terminal dictates the amount of air that is delivered to the space. When the zone thermostat indicates cooling is needed, the damper within the VAV terminal is opened and cool air is delivered. As the cooling demand decreases, the VAV terminal damper is closed to reduce the amount of cool air delivered. When the space is occupied, the damper will have a minimum airflow set point to ensure adequate ventilation air is provided to the space. If the space temperature is too cold with minimum air flow, the heating coil in the terminal unit is activated to satisfy the desired space conditions.
As each zone’s VAV terminal adjusts the amount of air delivered to the zone in response to the thermostat, the quantity of air that the central unit needs to supply to the system varies. The fan in the central unit utilizes a VFD to adjust the amount of air delivered based on the cumulative system demand from the zones. The response of the central fan to the variable demand for airflow at the zones allows fan energy to be conserved.
Precise temperature control: Allows independent zoning of spaces for optimal comfort.
Responsive: Ideal for buildings with different exposures, varying occupancy, or changing usage patterns.
Lower fan energy consumption: Modifying the fan speed at the central unit when dampers in the VAV terminals reduce airflow saves energy.
Centralized maintenance: Having the fan, cooling coil, and filters in single centralized location decreases the time required to service the system.
The system at minimum consists of:
A central unit housing a supply fan, coil(s), and filters: This unit conditions and distributes cool air to each zone VAV terminal.
VAV terminal (VAV box): Zone level unit containing a damper that regulates airflow in response to space conditions. In most cases, this unit also has a heating coil to modify the air delivery temperature.
Ductwork: Provides an airpath between the central unit and VAV terminals and from the terminals to the space.
Controls: Sensors, actuators, thermostats, etc. are digitally integrated to ensure the system provides the desired conditions to each of zones while not using more energy than necessary.
Single-Duct VAV: Modulates the amount of cool air from the central unit to the zone.
Single-Duct VAV with Reheat: Most common of the terminal units. A heating coil is added to the single duct VAV allowing heating to also occur at the zone.
Dual-Duct VAV: Hot and cold air from separate ducts are regulated at the terminal allowing for precise temperature control. Rarely used due to the extra expense associated with two supply air ducts.
Parallel Fan-Powered VAV: A fan is added to the single-duct VAV. Rarely used due to the extra expense associated with two supply air ducts. The fan is positioned to the side of the unit and does not operate unless the central fan is turned off and heating is needed. Primarily used in perimeter zones in cold climates.
Series Fan-Powered VAV: A fan is added to the single-duct VAV but operates any time the space is calling for less than 100% design cooling airflow. As the terminal damper closes to reduce cool air from the central unit, the fan draws air from the space and mixes it with the cool air to ensure space comfort. This unit allows constant air flow to the zone.
Single Zone VAV System: Adjusts fan airflow to maintain the defined space conditions.
Multi-zone VAV System: Utilizes terminal units to allow multiple zones to be served by a central unit. The central unit cools the air and distributes to the terminal units. The terminal units modulate the airflow and use a heating coil to provide simultaneous heating and cooling to different zones. The fan in the central unit is variable volume in response to system demand.
Both VAV systems save fan energy, whereas the multi-zone provides better zone control.
Initial costs: Higher installation costs compared to simpler HVAC systems especially attributed to controls.
Ventilation: Maintaining proper ventilation without incurring extra expense by over ventilating some of zones requires complex calculations and significant design time.
Space: Requires space for a larger central unit as well as longer duct runs and terminal units.
Noise control: Proper design is needed to minimize noise from fan powered VAV terminals.
AAON has addressed the two most common barriers associated with this system – lack of interior space for the central unit and the cost of customized controls. AAON RTUs be used as the central unit with AAON’s integrated multi-zone VAV controls. Integration of AAON controls reduces first cost compared to other systems. This allows multi-zone VAV to be a solution in applications where it was cost prohibitive in the past.
These same controls can also be integrated into other AAON equipment when used as the central cooling unit in a multi-zone VAV system. AAON AHUs provide best-in-class flexibility whether considering indoor units, outdoor units, packaged units or split units. With the many features available with an AAON unit and the convenience of customization, AAON can meet the specific needs of any building while providing assurance that both superior value and performance are attained.